2.1 Technical Specification Table
2.1 Technical Specification Table
Project | Specification | ||
---|---|---|---|
Control Characteristics | Control Mode | Sensorless Vector Control (SVC) | V/F Control |
Starting Torque | 0.5Hz/150% | 0.5Hz/100% | |
Speed Range | 1:100 | 1:50 | |
Speed Stability | ±0.5% | ±1% | |
Carrier Frequency | 0.5kHz~16kHz; Automatically adjusts carrier frequency according to load characteristics | ||
Overload Capacity | G Type: 150% rated current for 60s, 220% rated current for 1s P Type: 120% rated current for 60s, 150% rated current for 1s | ||
Torque Boost | 0.0% automatic torque boost; Manual torque boost 0.1%~30% | ||
Input/Output | Input Voltage Range | 220V/380V; Fluctuation Range: ±15% | |
Input Frequency Range | 50/60Hz; Fluctuation Range: ±5% | ||
Output Voltage Range | 0~Input Voltage, Error <5% | ||
Output Frequency Range | SVC: 0~320Hz; V/F: 0-3200Hz | ||
Operation Control | Operation Command Channel | 3 Channels: Operation Panel Set, Control Terminal Set, Serial Communication Port Set. Can be switched through multiple methods. | |
Frequency Source | Digital Set, Panel Potentiometer Set, Analog Voltage Set, Analog Current Set, Serial Communication Set, etc. Can be switched through multiple methods. | ||
Auxiliary Frequency Source | Multiple auxiliary frequency sources. Can perform frequency synthesis and frequency fine-tuning. | ||
Input Terminals | 7 Digital Input Terminals 2 Analog Input Terminals | ||
Output Terminals | 2 Open Collector Output Terminals 2 Relay Output Terminals 2 Analog Output Terminals | ||
Basic Functions | DC Braking Function | Braking Time: 0.0s~100.0s, Braking Action Current Value: 0.0%~100.0% | |
V/F Curve | 3 Types: Linear, Multipoint, Square | ||
Acceleration/Deceleration Curve | Linear or S-Curve Acceleration/Deceleration Mode; Four sets of acceleration/deceleration time; Acceleration/deceleration time range: 0.0~6500.0s | ||
Simple PLC, Multi-Speed | Achieve up to 16-speed operation through built-in PLC or control terminal | ||
Built-in PID | Convenient for realizing closed-loop control system for process control | ||
AVR Function | Automatically maintains constant output voltage when grid voltage changes | ||
Overvoltage, Overcurrent, and Overspeed Protection | Automatically limits current and voltage during operation to prevent frequent overcurrent and overvoltage tripping | ||
Quick Current Limiting Function | Minimizes overcurrent faults to improve system stability | ||
Torque Limitation and Control | “Excavator” characteristic, automatically limits torque during operation to prevent frequent overcurrent tripping | ||
Power-On Peripheral Device Safety Self-Check | Can perform a safety check on peripheral devices such as grounding and short circuits when powered on | ||
Timing Control Function | Set time range 0h~65535h | ||
Protection Functions | Output Phase Loss Protection, Overcurrent Protection, Overvoltage Protection, Undervoltage Protection, Overheat Protection, Overload Protection, Power-On Relay Fault Detection, etc. | ||
Display and Keyboard Operation | LED Display | 5-digit LED display | |
Parameter Lock Function | Set parameters are read-only controlled to prevent misoperation | ||
MF.K Key | Programmable Key: Command Channel Switching/Forward and Reverse Operation/Incremental Operation Function Selection/Menu Mode Switching | ||
Environmental Conditions | Usage Place | Indoors, not exposed to direct sunlight, no dust, corrosive gases, flammable gases, oil mist, water vapor, dripping water, or salt | |
Altitude | Below 1000m; Above 1000m, use with derating, derate 1% for every 100m increase | ||
Ambient Temperature | -10°C~40°C, derate usage when temperature exceeds 40°C, derate 1% for every 1°C increase in ambient temperature, maximum ambient temperature for use is 50°C | ||
Humidity | ≤95%RH, avoid frost | ||
Vibration | Vibration acceleration less than 0.6g | ||
Storage Temperature | -25°C~+60°C |
NEXT