2.1 Technical Specification Table

Project Specification
Control Characteristics Control Mode Sensorless Vector Control (SVC) V/F Control
Starting Torque 0.5Hz/150% 0.5Hz/100%
Speed Range 1:100 1:50
Speed Stability ±0.5% ±1%
Carrier Frequency 0.5kHz~16kHz; Automatically adjusts carrier frequency according to load characteristics
Overload Capacity G Type: 150% rated current for 60s, 220% rated current for 1s
P Type: 120% rated current for 60s, 150% rated current for 1s
Torque Boost 0.0% automatic torque boost; Manual torque boost 0.1%~30%
Input/Output Input Voltage Range 220V/380V; Fluctuation Range: ±15%
Input Frequency Range 50/60Hz; Fluctuation Range: ±5%
Output Voltage Range 0~Input Voltage, Error <5%
Output Frequency Range SVC: 0~320Hz; V/F: 0-3200Hz
Operation Control Operation Command Channel 3 Channels: Operation Panel Set, Control Terminal Set, Serial Communication Port Set. Can be switched through multiple methods.
Frequency Source Digital Set, Panel Potentiometer Set, Analog Voltage Set, Analog Current Set, Serial Communication Set, etc. Can be switched through multiple methods.
Auxiliary Frequency Source Multiple auxiliary frequency sources. Can perform frequency synthesis and frequency fine-tuning.
Input Terminals 7 Digital Input Terminals
2 Analog Input Terminals
Output Terminals 2 Open Collector Output Terminals
2 Relay Output Terminals
2 Analog Output Terminals
Basic Functions DC Braking Function Braking Time: 0.0s~100.0s, Braking Action Current Value: 0.0%~100.0%
V/F Curve 3 Types: Linear, Multipoint, Square
Acceleration/Deceleration Curve Linear or S-Curve Acceleration/Deceleration Mode; Four sets of acceleration/deceleration time; Acceleration/deceleration time range: 0.0~6500.0s
Simple PLC, Multi-Speed Achieve up to 16-speed operation through built-in PLC or control terminal
Built-in PID Convenient for realizing closed-loop control system for process control
AVR Function Automatically maintains constant output voltage when grid voltage changes
Overvoltage, Overcurrent, and Overspeed Protection Automatically limits current and voltage during operation to prevent frequent overcurrent and overvoltage tripping
Quick Current Limiting Function Minimizes overcurrent faults to improve system stability
Torque Limitation and Control “Excavator” characteristic, automatically limits torque during operation to prevent frequent overcurrent tripping
Power-On Peripheral Device Safety Self-Check Can perform a safety check on peripheral devices such as grounding and short circuits when powered on
Timing Control Function Set time range 0h~65535h
Protection Functions Output Phase Loss Protection, Overcurrent Protection, Overvoltage Protection, Undervoltage Protection, Overheat Protection, Overload Protection, Power-On Relay Fault Detection, etc.
Display and Keyboard Operation LED Display 5-digit LED display
Parameter Lock Function Set parameters are read-only controlled to prevent misoperation
MF.K Key Programmable Key: Command Channel Switching/Forward and Reverse Operation/Incremental Operation Function Selection/Menu Mode Switching
Environmental Conditions Usage Place Indoors, not exposed to direct sunlight, no dust, corrosive gases, flammable gases, oil mist, water vapor, dripping water, or salt
Altitude Below 1000m; Above 1000m, use with derating, derate 1% for every 100m increase
Ambient Temperature -10°C~40°C, derate usage when temperature exceeds 40°C, derate 1% for every 1°C increase in ambient temperature, maximum ambient temperature for use is 50°C
Humidity ≤95%RH, avoid frost
Vibration Vibration acceleration less than 0.6g
Storage Temperature -25°C~+60°C