Inverter Peripheral Electrical Component Selection Table
Inverter Power | Circuit Breaker (MCCB) A | Recommended Contactor A | Recommended Input Side Main Circuit Wire mm² | Recommended Output Side Main Circuit Wire mm² | Recommended Control Circuit Wire mm² |
---|---|---|---|---|---|
0.4KWT2 | 16 | 10 | 2.5 | 2.5 | 1.0 |
0.7KWT2 | 16 | 10 | 2.5 | 2.5 | 1.0 |
1.5KWT2 | 20 | 16 | 4.0 | 2.5 | 1.0 |
2.2KWT2 | 32 | 20 | 6.0 | 4.0 | 1.0 |
0.7KWT4 | 10 | 10 | 2.5 | 2.5 | 1.0 |
1.5KWT4 | 16 | 10 | 2.5 | 2.5 | 1.0 |
2.2KWT4 | 16 | 10 | 2.5 | 2.5 | 1.0 |
3.7KWT4 | 25 | 16 | 4.0 | 4.0 | 1.0 |
5.5KWT4 | 32 | 25 | 4.0 | 4.0 | 1.0 |
7.5KWT4 | 40 | 32 | 4.0 | 4.0 | 1.0 |
11KWT4 | 63 | 40 | 4.0 | 4.0 | 1.0 |
15KWT4 | 63 | 40 | 6.0 | 6.0 | 1.0 |
18.5KWT4 | 100 | 63 | 6 | 6 | 1.5 |
22KWT4 | 100 | 63 | 10 | 10 | 1.5 |
30KWT4 | 125 | 100 | 16 | 10 | 1.5 |
37KWT4 | 160 | 100 | 16 | 16 | 1.5 |
45KWT4 | 200 | 125 | 25 | 25 | 1.5 |
55KWT4 | 200 | 125 | 35 | 25 | 1.5 |
75KWT4 | 250 | 160 | 50 | 35 | 1.5 |
90KWT4 | 250 | 160 | 70 | 35 | 1.5 |
110KWT4 | 350 | 350 | 120 | 120 | 1.5 |
132KWT4 | 400 | 400 | 150 | 150 | 1.5 |
160KWT4 | 500 | 400 | 185 | 185 | 1.5 |
200KWT4 | 600 | 600 | 150*2 | 150*2 | 1.5 |
220KWT4 | 600 | 600 | 150*2 | 150*2 | 1.5 |
250KWT4 | 800 | 600 | 185*2 | 185*2 | 1.5 |
280KWT4 | 800 | 800 | 185*2 | 185*2 | 1.5 |
315KWT4 | 800 | 800 | 150*3 | 150*3 | 1.5 |
355KWT4 | 800 | 800 | 150*4 | 150*4 | 1.5 |
400KWT4 | 1000 | 1000 | 150*4 | 150*4 | 1.5 |