3.4 Control terminal and function

Category Terminal Symbol Terminal Name Function Description
Power +10V-GND +10V Power Provides +10V power externally, maximum output current: 20mA, typically used as the operating power supply for external potentiometers
Power +24V-COM +24V Power Provides +24V power externally, maximum output current: 150mA, generally used as the power supply for digital input-output terminals and external sensor power
Power OP External Power Input Terminal Connects to +24V or COM through the connection piece on the control board (factory default connection to +24V)
When driving DI1~DI6 with external signals, OP needs to be connected to an external power source, and the short-circuit connection piece between OP and 24V should be removed
Analog Input AI1-GND Analog Input Terminal 1 1. Input Range: DC 0V~10V/0mA, selected by parameter P4-37 for voltage or current input.
2. Input Impedance: 22kΩ for voltage input, 500Ω for current input
Analog Input AI2-GND Analog Input Terminal 2 1. Input Range: DC 0V~10V/0mA, selected by parameter P4-37 for voltage or current input.
2. Input Impedance: 22kΩ for voltage input, 500Ω for current input
Digital Input X1, X2, X3, X4, X5, X6, X7 Digital Input 1, 2, 3, 4, 5, 6, 7 1. Opto-isolation
2. Input Impedance: 4kΩ
Input Voltage Range: 9V~30V
Analog Output AO1-GND Analog Output 1 AO1, AO2 are selected for voltage or current output by jumpers J3 and J2 on the control board
Output Voltage Range: 0V~10V
Output Current Range: 0mA~20mA
Factory default is voltage output
Analog Output AO2-GND (shared with Y1 for models below 18.5kW, selected by jumpers) Analog Output 2 AO1, AO2 are selected for voltage or current output by jumpers J3 and J2 on the control board
Output Voltage Range: 0V~10V
Output Current Range: 0mA~20mA
Factory default is voltage output
Digital Output HD0 High-Speed Pulse Output Collector-Emitter Open Circuit Output 1. Opto-isolation, bipolar open circuit collector output.
2. Output Voltage Range: 0V~24V
Output Current Range: 0mA~50mA
(Note: For models of 18.5kW and below, Y1 function can be switched to analog output by jumpers)
Digital Output Y1 Digital Output 1
Analog Voltage Output 2
1. Opto-isolation, bipolar open circuit collector output.
2. Output Voltage Range: 0V~24V
Output Current Range: 0mA~50mA
(Note: For models of 18.5kW and below, Y1 function can be switched to analog output by jumpers)
Relay Output K1A-K1B, K2A-K2B Normally Closed Terminals Contact Drive Capacity:
AC 250V, 3A; DC 30V, 1A
Relay Output K1A-K1C, K2A-K2C Normally Open Terminals Contact Drive Capacity:
AC 250V, 3A; DC 30V, 1A
RS485 Communication RS+ RS485 Communication Terminal Positive RS485 Differential Signal Positive Terminal
RS485 Communication RS- RS485 Communication Terminal Negative RS485 Differential Signal Negative Terminal