5.3 P2 Group Vector Parameters

ℹ️
Inverter Parameter Attribute Description
✅: Indicates that the parameter setting value can be changed when the inverter is in both stopped and running states.
✳️: Indicates that the parameter setting value cannot be changed when the inverter is in a running state.
❎: Indicates that the parameter value is the actual measured recording value and cannot be changed.

P2 Group: Vector Parameters

Function Code Name Setting Range Factory Value Attribute DEC Address
P2-00 Speed Loop Proportional Gain 1 1~100 30 61952
P2-01 Speed Loop Integral Time 1 0.01~10.00s 0.50s 61953
P2-02 Switching Frequency 1 0.00~P2-05 5.00Hz 61954
P2-03 Speed Loop Proportional Gain 2 1~100 20 61955
P2-04 Speed Loop Integral Time 2 0.01~10.00s 1.00s 61956
P2-05 Switching Frequency 2 P2-2~Maximum Frequency 10.00Hz 61957
P2-06 Vector Control Torque Differential Gain 50%~200% 150% 61958
P2-07 Speed Loop Filter Time Constant 0.000~0.100s 0.000s 61959
P2-08 Vector Control Overexcitation Gain 0~200 64 61960
P2-09 Torque Upper Limit Source Under Speed Control 0: Set by Function Code P2-10
1: AI1
2: AI2
3: Keyboard Potentiometer
4: PULSE Pulse Setting
5: Communication Setting
6: MIN(AI1, AI2)
7: MAX(AI1, AI2)
Full Scale Corresponding to Options 1-7 P2-10
0 61961
P2-10 Torque Upper Limit Digital Setting Under Speed Control 0.0%~200.0% 150.0% 61962
P2-13 Excitation Adjustment Proportional Gain 0~60000 2000 61965
P2-14 Excitation Adjustment Integral Gain 0~60000 1300 61966
P2-15 Torque Adjustment Proportional Gain 0~60000 2000 61967
P2-16 Torque Adjustment Integral Gain 0~60000 1300 61968
P2-17 Speed Loop Integral Property Units: Integral Separation
0: Invalid
1: Valid
0 61969