5.7 P6 Group Start-Stop Control Parameters
5.7 P6 Group Start-Stop Control Parameters
ℹ️
Inverter Parameter Attribute Description
- ✅: Indicates that the setting value of this parameter can be changed when the inverter is in stop or run state.
- ✳️: Indicates that the setting value of this parameter cannot be changed when the inverter is in run state.
- ❎: Indicates that the value of this parameter is the actual measured value and cannot be changed.
P6 Group: Start-Stop Control Parameters
Function Code | Name | Setting Range | Factory Value | Attribute | DEC Address |
---|---|---|---|---|---|
P6-00 | Start Mode | 0: Direct Start 1: Speed Tracking Restart 2: Pre-excitation Start (AC asynchronous machine) |
0 | ✅ | 62976 |
P6-01 | Speed Tracking Mode | 0: Start from Stop Frequency 1: Start from Zero Speed 2: Start from Max Frequency |
0 | ✳️ | 62977 |
P6-02 | Speed Tracking Acceleration/Deceleration | 1~100 | 20 | ✅ | 62978 |
P6-03 | Start Frequency | 0~P0-08 | 0.00Hz | ✅ | 62979 |
P6-04 | Start Frequency Holding Time | 0.0s~100.0s | 0.0s | ✳️ | 62980 |
P6-05 | Start DC Brake Current/Pre-excitation Current | 0%~100% | 0% | ✳️ | 62981 |
P6-06 | Start DC Brake Time/Pre-excitation Time | 0.0s~100.0s | 0.0s | ✳️ | 62982 |
P6-07 | Acceleration/Deceleration Mode | 0: Linear Acceleration/Deceleration 1: S-curve Acceleration/Deceleration A 2: S-curve Acceleration/Deceleration B |
0 | ✳️ | 62983 |
P6-08 | S-curve Start Segment Time Ratio | 0.0%~(100.0%-P6-09) | 30.0% | ✳️ | 62984 |
P6-09 | S-curve End Segment Time Ratio | 0.0%~(100.0%-P6-08) | 30.0% | ✅ | 62985 |
P6-10 | Stop Mode | 0: Deceleration Stop 1: Free Stop |
0 | ✅ | 62986 |
P6-11 | Stop DC Brake Start Frequency | 0.00Hz~Max Frequency | 0.00Hz | ✅ | 62987 |
P6-12 | Stop DC Brake Wait Time | 0.0s~100.0s | 0.0s | ✅ | 62988 |
P6-13 | Stop DC Brake Current | 0%~100% | 0% | ✅ | 62989 |
P6-14 | Stop DC Brake Time | 0.0s~100.0s | 0.0s | ✅ | 62990 |
P6-15 | Brake Usage Rate | 0%~100% | 100% | ✅ | 62991 |