5.7 P6 Group Start-Stop Control Parameters

ℹ️
Inverter Parameter Attribute Description
  • ✅: Indicates that the setting value of this parameter can be changed when the inverter is in stop or run state.
  • ✳️: Indicates that the setting value of this parameter cannot be changed when the inverter is in run state.
  • ❎: Indicates that the value of this parameter is the actual measured value and cannot be changed.

P6 Group: Start-Stop Control Parameters

Function Code Name Setting Range Factory Value Attribute DEC Address
P6-00 Start Mode 0: Direct Start
1: Speed Tracking Restart
2: Pre-excitation Start (AC asynchronous machine)
0 62976
P6-01 Speed Tracking Mode 0: Start from Stop Frequency
1: Start from Zero Speed
2: Start from Max Frequency
0 ✳️ 62977
P6-02 Speed Tracking Acceleration/Deceleration 1~100 20 62978
P6-03 Start Frequency 0~P0-08 0.00Hz 62979
P6-04 Start Frequency Holding Time 0.0s~100.0s 0.0s ✳️ 62980
P6-05 Start DC Brake Current/Pre-excitation Current 0%~100% 0% ✳️ 62981
P6-06 Start DC Brake Time/Pre-excitation Time 0.0s~100.0s 0.0s ✳️ 62982
P6-07 Acceleration/Deceleration Mode 0: Linear Acceleration/Deceleration
1: S-curve Acceleration/Deceleration A
2: S-curve Acceleration/Deceleration B
0 ✳️ 62983
P6-08 S-curve Start Segment Time Ratio 0.0%~(100.0%-P6-09) 30.0% ✳️ 62984
P6-09 S-curve End Segment Time Ratio 0.0%~(100.0%-P6-08) 30.0% 62985
P6-10 Stop Mode 0: Deceleration Stop
1: Free Stop
0 62986
P6-11 Stop DC Brake Start Frequency 0.00Hz~Max Frequency 0.00Hz 62987
P6-12 Stop DC Brake Wait Time 0.0s~100.0s 0.0s 62988
P6-13 Stop DC Brake Current 0%~100% 0% 62989
P6-14 Stop DC Brake Time 0.0s~100.0s 0.0s 62990
P6-15 Brake Usage Rate 0%~100% 100% 62991