5.11 PA Group PID Function Parameters

ℹ️
Inverter Parameter Attribute Explanation
✅: Indicates that the setting value of this parameter can be changed when the inverter is in both stop and running states;
✳️: Indicates that the setting value of this parameter cannot be changed when the inverter is in a running state;
❎: Indicates that the value of this parameter is an actual detection record value and cannot be changed.

PA Group: PID Function Parameters

Function Code Name Setting Range Factory Value Attribute DEC Address
PA-00 PID Setpoint Source 0: Set by PA-01
1: AI1
2: AI2
3: External Keyboard Potentiometer for AI3
4: HDI Input Pulse Setting (X5)
5: Communication Setpoint
6: Multi-segment Instruction Setpoint
7: Pressure Setpoint from Supply Group b0-01
0 64000
PA-01 PID Value Setting 0.0~100.0% 50.0% 64001
PA-02 PID Feedback Source 0: AI1
1: AI2
2: External Keyboard Potentiometer for AI3
3: AI1-AI2
4: HDI Input Pulse Setting (X5)
5: Communication Setpoint
6: AI1+AI2
7: MAX(AI1,AI2)
8: MIN(AI1,AI2)
0 64002
PA-03 PID Action Direction 0: Direct Action
1: Reverse Action
0 64003
PA-04 PID Setpoint Feedback Range 0~65535 1000 64004
PA-05 Proportional Gain KP1 0.0~100.0 20.0 64005
PA-06 Integral Time Ti1 0.01~10.00s 2.00s 64006
PA-07 Derivative Time Td1 0.000~10.000s 0.000s 64007
PA-08 PID Reverse Cutoff Frequency 0.00~Maximum Frequency 2.00Hz 64008
PA-09 PID Deviation Limit 0.0~100.0% 0.0% 64009
PA-10 PID Integral Limit 0.00~100.00% 0.1% 64010
PA-11 PID Setpoint Change Time 0.00~650.00s 0.00s 64011
PA-12 PID Feedback Filtering Time 0.00~60.00s 0.00s 64012
PA-13 PID Output Filtering Time 0.00~60.00s 0.00s 64013
PA-15 Proportional Gain KP2 0.0~100.0 20.0 64015
PA-16 Integral Time Ti2 0.01~10.00s 2.00s 64016
PA-17 Derivative Time Td2 0.000~10.000s 0.000s 64017
PA-18 PID Parameter Switching Condition 0: No Switching
1: Switching by X Terminal
2: Automatic Switching Based on Deviation
0 64018
PA-19 PID Parameter Switching Deviation 1 0.0%~PA-20 20.0% 64019
PA-20 PID Parameter Switching Deviation 2 PA-19~100.0% 80.0% 64020
PA-21 Initial Value of PID 0.0~100.0% 0.0% 64021
PA-22 PID Initial Value Holding Time 0.00~650.00s 0.00s 64022
PA-23 Maximum Forward Deviation of Two Successive Outputs 0.00~100.00% 1.00% 64023
PA-24 Maximum Reverse Deviation of Two Successive Outputs 0.00~100.00% 1.00% 64024
PA-25 PID Integral Attribute Units: Integral Separation
0: Invalid
1: Valid
Tens: Stop Integral After Output Limit Reached
0: Continue Integration
1: Stop Integration
00 64025
PA-26 PID Feedback Loss Detection Value 0.0%: No Feedback Loss Judgment
0.1~100.0%
0.0% 64026
PA-27 PID Feedback Loss Detection Time 0.0s~20.0s 0.0s 64027
PA-28 PID Stop Calculation 0: No Calculation on Stop
1: Calculation on Stop
1 64028