5.11 PA Group PID Function Parameters
5.11 PA Group PID Function Parameters
ℹ️
Inverter Parameter Attribute Explanation
✳️: Indicates that the setting value of this parameter cannot be changed when the inverter is in a running state;
❎: Indicates that the value of this parameter is an actual detection record value and cannot be changed.
PA Group: PID Function Parameters
Function Code | Name | Setting Range | Factory Value | Attribute | DEC Address |
---|---|---|---|---|---|
PA-00 | PID Setpoint Source | 0: Set by PA-01 1: AI1 2: AI2 3: External Keyboard Potentiometer for AI3 4: HDI Input Pulse Setting (X5) 5: Communication Setpoint 6: Multi-segment Instruction Setpoint 7: Pressure Setpoint from Supply Group b0-01 |
0 | ✅ | 64000 |
PA-01 | PID Value Setting | 0.0~100.0% | 50.0% | ✅ | 64001 |
PA-02 | PID Feedback Source | 0: AI1 1: AI2 2: External Keyboard Potentiometer for AI3 3: AI1-AI2 4: HDI Input Pulse Setting (X5) 5: Communication Setpoint 6: AI1+AI2 7: MAX(AI1,AI2) 8: MIN(AI1,AI2) |
0 | ✅ | 64002 |
PA-03 | PID Action Direction | 0: Direct Action 1: Reverse Action |
0 | ✅ | 64003 |
PA-04 | PID Setpoint Feedback Range | 0~65535 | 1000 | ✅ | 64004 |
PA-05 | Proportional Gain KP1 | 0.0~100.0 | 20.0 | ✅ | 64005 |
PA-06 | Integral Time Ti1 | 0.01~10.00s | 2.00s | ✅ | 64006 |
PA-07 | Derivative Time Td1 | 0.000~10.000s | 0.000s | ✅ | 64007 |
PA-08 | PID Reverse Cutoff Frequency | 0.00~Maximum Frequency | 2.00Hz | ✅ | 64008 |
PA-09 | PID Deviation Limit | 0.0~100.0% | 0.0% | ✅ | 64009 |
PA-10 | PID Integral Limit | 0.00~100.00% | 0.1% | ✅ | 64010 |
PA-11 | PID Setpoint Change Time | 0.00~650.00s | 0.00s | ✅ | 64011 |
PA-12 | PID Feedback Filtering Time | 0.00~60.00s | 0.00s | ✅ | 64012 |
PA-13 | PID Output Filtering Time | 0.00~60.00s | 0.00s | ✅ | 64013 |
PA-15 | Proportional Gain KP2 | 0.0~100.0 | 20.0 | ✅ | 64015 |
PA-16 | Integral Time Ti2 | 0.01~10.00s | 2.00s | ✅ | 64016 |
PA-17 | Derivative Time Td2 | 0.000~10.000s | 0.000s | ✅ | 64017 |
PA-18 | PID Parameter Switching Condition | 0: No Switching 1: Switching by X Terminal 2: Automatic Switching Based on Deviation |
0 | ✅ | 64018 |
PA-19 | PID Parameter Switching Deviation 1 | 0.0%~PA-20 | 20.0% | ✅ | 64019 |
PA-20 | PID Parameter Switching Deviation 2 | PA-19~100.0% | 80.0% | ✅ | 64020 |
PA-21 | Initial Value of PID | 0.0~100.0% | 0.0% | ✅ | 64021 |
PA-22 | PID Initial Value Holding Time | 0.00~650.00s | 0.00s | ✅ | 64022 |
PA-23 | Maximum Forward Deviation of Two Successive Outputs | 0.00~100.00% | 1.00% | ✅ | 64023 |
PA-24 | Maximum Reverse Deviation of Two Successive Outputs | 0.00~100.00% | 1.00% | ✅ | 64024 |
PA-25 | PID Integral Attribute | Units: Integral Separation 0: Invalid 1: Valid Tens: Stop Integral After Output Limit Reached 0: Continue Integration 1: Stop Integration |
00 | ✅ | 64025 |
PA-26 | PID Feedback Loss Detection Value | 0.0%: No Feedback Loss Judgment 0.1~100.0% |
0.0% | ✅ | 64026 |
PA-27 | PID Feedback Loss Detection Time | 0.0s~20.0s | 0.0s | ✅ | 64027 |
PA-28 | PID Stop Calculation | 0: No Calculation on Stop 1: Calculation on Stop |
1 | ✅ | 64028 |