5.6 P5 Group Output Terminal Parameters

ℹ️
Inverter Parameter Attribute Description
  • ✅: Indicates that the setting value of this parameter can be changed when the inverter is in both stopped and running states.
  • ✳️: Indicates that the setting value of this parameter cannot be changed when the inverter is in a running state.
  • ❎: Indicates that the value of this parameter is the actual measured value, which cannot be changed.

P5 Group: Output Terminal Parameters

Function Code Name Setting Range Factory Value Attribute DEC Address
P5-00 HDO Terminal Output Mode Selection 0: High-speed pulse output (HDO)
1: Terminal switch output (FMR)
0 62720
P5-01 HDO Terminal Switch Output Function Selection (FMR) 0: No output
1: Inverter running
2: Fault output (fault stop)
3: Frequency level detection FDT1 output
4: Frequency reached
5: Zero speed operation (no output when stopped)
6: Motor overload pre-alarm
7: Inverter overload pre-alarm
8: Set count value reached
9: Specified count value reached
11: PLC cycle completed
12: Cumulative running time reached
13: Frequency limit
14: Torque limit
15: Ready for operation
16: AI1 > AI2
17: Upper limit frequency reached
18: Lower limit frequency reached (related to operation)
19: Undervoltage status output
20: Communication setting
23: Zero speed operation 2 (output even when stopped)
24: Cumulative power-on time reached
25: Frequency level detection FDT2 output
26: Frequency 1 reached output
27: Frequency 2 reached output
28: Current 1 reached output
29: Current 2 reached output
30: Time-out reached output
31: AI1 input out of range
32: No-load
33: Reverse operation
34: Zero current state
35: Module temperature reached
36: Output current exceeded
37: Lower limit frequency reached (output even when stopped)
38: Alarm output (continue running)
40: This run time reached
41: Fault output (fault for free stop and undervoltage not output)
42: Frequency 1 ≤ operating frequency ≤ frequency 2
43: Frequency 1 ≥ operating frequency ≥ frequency 2
44: Frequency 1 ≤ set frequency ≤ frequency 2
45: Frequency 1 ≥ set frequency ≥ frequency 2
46: Linkage X1 terminal output
47: Linkage X2 terminal output
48: Linkage X3 terminal output
49: Linkage X4 terminal output
50: Auxiliary motor pump 1
51: Auxiliary motor pump 2
52: Auxiliary motor pump 3
53: Auxiliary motor pump 4
0 62721
P5-02 Relay RY1 Function Selection (K1A-K1B-K1C) Same as P5-01 2 62722
P5-03 Relay RY2 Function Selection (K2A-K2B-K2C) Same as P5-01 0 62723
P5-04 Y1 Output Function Selection Same as P5-01 1 62724
P5-06 HDO High-speed Pulse Output Function Selection 0: Running frequency
1: Set frequency
2: Output current
3: Output torque
4: Output power
5: Output voltage
6: HDI pulse input (100.0% corresponds to 100.0 kHz)
7: AI1
8: AI2
9: AI3
11: Count value
12: Communication setting
13: Motor speed
14: Output current (100.0% corresponds to 1000.0 A)
15: Output voltage (100.0% corresponds to 1000.0 V)
16: Reserved
17: Inverter output torque
0 62726
P5-07 AO1 Output Function Selection Same as P5-06 0 62727
P5-08 AO2 Output Function Selection Same as P5-06 0 62728
P5-09 HDO Output Maximum Frequency 0.01 kHz to 50.00 kHz 50.00 kHz 62729
P5-10 AO1 Zero Offset Coefficient -100.00% to +100.00% 0.0% 62730
P5-11 AO1 Gain -10.00 to +10.00 1.00 62731
P5-12 AO2 Zero Offset Coefficient -100.00% to +100.00% 0.0% 62732
P5-13 AO2 Gain -10.00 to +10.00 1.00 62733
P5-17 FMR Delay Close Time 0.0 s to 6553.5 s 0.0 s 62737
P5-18 RY1 Delay Close Time 0.0 s to 6553.5 s 0.0 s 62738
P5-19 RY2 Delay Close Time 0.0 s to 6553.5 s 0.0 s 62739
P5-20 Y1 Delay Close Time 0.0 s to 6553.5 s 0.0 s 62740
P5-21 Reserved - - - 62741
P5-22 Y Terminal Output Active State Selection 0: Positive logic
1: Negative logic
Individual digits: HDO terminal
Tens: RY1
Hundreds: RY2
Thousands: Y1
Ten Thousands: Reserved
00000 62742
P5-23 AO Current Output Selection Individual digits: AO1
Tens: AO2
0: 0~20 mA
1: 4~20 mA
00 62743
P5-24 FMR Delay Open Time 0.0 s to 6553.5 s 0.0 s 62744
P5-25 RY1 Delay Open Time 0.0 s to 6553.5 s 0.0 s
P5-26 RY2 Delay Open Time 0.0 s - 6553.5 s 0.0 s 62746
P5-27 Y1 Delay Open Time 0.0 s - 6553.5 s 0.0 s 62747