5.8 P7 Group Keyboard and Display

ℹ️
Inverter Parameter Attribute Description
  • ✅: Indicates that the setting value of this parameter can be changed when the inverter is in stop or run state.
  • ✳️: Indicates that the setting value of this parameter cannot be changed when the inverter is in run state.
  • ❎: Indicates that the value of this parameter is the actual measured value and cannot be changed.

P7 Group: Keyboard and Display

Function Code Name Setting Range Factory Value Attribute DEC Address
P7-01 MF.K Key Function Selection 0: MF.K Disabled
1: Switch between Panel Command Channel and Remote Command Channel (Terminal Command Channel or Communication Command Channel)
2: Forward/Reverse Switching
3: Forward Jog
4: Reverse Jog
2 63233
P7-02 STOP/RESET Key Function 0: STOP/RESET Key Stop Function Only Available in Keyboard Operation Mode
1: STOP/RESET Key Stop Function Available in Any Situation
1 63234
P7-03 LED Running Display Parameter 1 0000~FFFF
Bit00: Running Frequency 1 (Hz)
Bit01: Set Frequency (Hz)
Bit02: DC Bus Voltage (V)
Bit03: Output Voltage (V)
Bit04: Output Current (A)
Bit05: Output Power (KW)
Bit06: Output Torque (%)
Bit07: X Input Status
Bit08: Y Output Status
Bit09: AI1 Voltage (V)
Bit10: AI2 Voltage (V)
Bit11: AI3 Panel Potentiometer Voltage (V)
Bit12: Count Value
Bit13: Reserved
Bit14: Load Speed Display
Bit15: PID Setting (Supply Macro Display Pressure Value)
001F 63235
P7-04 LED Running Display Parameter 2 0000~FFFF
Bit00: PID Feedback (Supply Macro Display Pressure Value)
Bit01: PLC Stage
Bit02: HDI Input Pulse Frequency (kHz)
Bit03: Running Frequency 2 (Hz)
Bit04: Remaining Running Time
Bit05: AI1 Voltage Before Calibration (V)
Bit06: AI2 Voltage Before Calibration (V)
Bit07: AI3 Panel Potentiometer Voltage Before Calibration (V)
Bit08: Line Speed
Bit09: Current Power On Time (Hour)
Bit10: Current Running Time (Min)
Bit11: HDI Input Pulse Frequency (Hz)
Bit12: Communication Setting Value
Bit13: Encoder Feedback Speed (Hz)
Bit14: Main Frequency X Display (Hz)
Bit15: Auxiliary Frequency Y Display (Hz)
63236
P7-05 LED Stop Display Parameter 0000~FFFF
Bit00: Set Frequency (Hz)
Bit01: DC Bus Voltage (V)
Bit02: X Input Status
Bit03: Y Output Status
Bit04: AI1 Voltage (V)
Bit05: AI2 Voltage (V)
Bit06: AI3 Panel Potentiometer Voltage (V)
Bit07: Count Value
Bit08: Length Value
Bit09: PLC Stage
Bit10: Load Speed
Bit11: PID Setting (Pressure)
Bit12: HDI Input Pulse Frequency (Hz)
Bit13: PID Feedback (Pressure) (Hz)
0033 63237
P7-06 Load Speed Display Coefficient 0.0001~6.5000 1.000 63238
P7-07 Inverter Module Heat Sink Temperature 0.0℃~100.0℃ - 63239
P7-09 Total Running Time 0h~65535h - 63241
P7-12 Load Speed Display Decimal Point Position 0: 0 Decimal Places
1: 1 Decimal Place
2: 2 Decimal Places
3: 3 Decimal Places
1 63244
P7-13 Total Power On Time 0~65535h - 63245
P7-14 Total Power Consumption 0~65535 Degrees - 63246
P7-17 Digital Display 2 Stop Monitoring Selection 0000~FFFF 0000 63249
P7-18 Digital Display 2 Running Monitoring Selection 0000~FFFF 0000 63250