5.17 b0 Group Intelligent Constant Pressure Water Supply Parameters
5.17 b0 Group Intelligent Constant Pressure Water Supply Parameters
ℹ️
Variable Frequency Drive Parameter Property Description
✳️: Indicates that the setting value of this parameter cannot be changed when the VFD is in a running state;
❎: Indicates that the value of this parameter is an actual detection record value and cannot be changed;
b0 Group: Intelligent Variable Frequency Constant Pressure Water Supply Parameters
Function Code | Name | Setting Range | Factory Value | Property | DEC Address |
---|---|---|---|---|---|
b0-00 | Pressure Sensor Range | 0~99.99 Bar (kg) | 10.00 | ✅ | 45056 |
b0-01 | Target Pressure Digital SettingNote: Target pressure determined by PA-01 | 0~99.99 Bar (kg) | 5.00 | ✅ | 45057 |
b0-02 | Sleep Pressure | 0~100.0% (Linked proportionally to target pressure) | 100.0% | ✅ | 45058 |
b0-03 | Wake-up Pressure | 0~100.0% (Linked proportionally to target pressure) | 95.0% | ✅ | 45059 |
b0-04 | Pressure Stability Deviation | 0~100.0% (Linked proportionally to target pressure) | 2.0% | ✅ | 45060 |
b0-05 | Sleep Delay | 0~6553.5s (0: Sleep mode off) | 20.0s | ✅ | 45061 |
b0-06 | Wake-up Delay | 0~6553.5s | 0.0s | ✅ | 45062 |
b0-07 | Pressure Upper Limit Protection Value | 0~100.0% (Linked proportionally to target pressure) | 10.0% | ✅ | 45063 |
b0-08 | Pressure Upper Limit Protection Shutdown Delay | 0~6553.5s (0: Disable detection) | 0.3s | ✅ | 45064 |
b0-09 | Frequency Below Target Pressure Protection Delay | 0~6553.5s (0: Disable detection) | 3.0s | ✅ | 45065 |
b0-10 | Auxiliary Pump Quantity Setting | 0~4 (0: Disable one-to-many control) | 0 | ✅ | 45066 |
b0-11 | Auxiliary Pump Pressure Tolerance | 0~100.0% (Linked proportionally to target pressure) | 5.0% | ✅ | 45067 |
b0-12 | Auxiliary Pump Start Delay | 0~6553.5s | 30.0s | ✅ | 45068 |
b0-13 | Auxiliary Pump Pressure Reduction Tolerance | 0~100.0% (Linked proportionally to target pressure) | 5.0% | ✅ | 45069 |
b0-14 | Auxiliary Pump Stop Delay | 0~6553.5s | 30.0s | ✅ | 45070 |
b0-15 | Pressure Upper Limit Emergency Auxiliary Pump Reduction Delay(Preempts normal pump reduction time of b0-14) | 0~6553.5s | 3.0s | ✅ | 45071 |