5.5 P4 Group Input Terminal Parameters

ℹ️
Inverter Parameter Attribute Description
✅: Indicates that the parameter setting value can be changed when the inverter is in both stopped and running states.
✳️: Indicates that the parameter setting value cannot be changed when the inverter is in a running state.
❎: Indicates that the parameter value is the actual measured recording value and cannot be changed.

P4 Group: Input Terminal Parameters

Function Code Name Setting Range Factory Value Attribute DEC Address
P4-00 X1 Terminal Function Selection 0: No function
1: Forward Run (FWD)
2: Reverse Run (REV)
3: Three-wire Run Control
4: Forward Jog (FJOG)
5: Reverse Jog (RJOG)
6: UP Terminal
7: DOWN Terminal
8: Free Stop
9: Fault Reset (RESET)
10: Run Pause
11: External Fault Normally Open Input
12: Multi-segment Instruction Terminal 1
13: Multi-segment Instruction Terminal 2
14: Multi-segment Instruction Terminal 3
15: Multi-segment Instruction Terminal 4
16: Acceleration/Deceleration Time Selection Terminal 1
17: Acceleration/Deceleration Time Selection Terminal 2
18: Frequency Switching
19: UP/DOWN Setting Clear (Terminal/Keyboard)
20: Run Command Switching Terminal 1
21: Acceleration/Deceleration Prohibition
22: PID Pause
23: PLC State Reset
24: Swing Pause
25: Counter Input
26: Counter Reset
27: Length Counter Input
28: Length Reset
29: Torque Control Prohibition
30: HDI Pulse Frequency Input (X5)
31: Reserved
32: Immediate DC Braking
33: External Fault Normally Closed Input
34: Frequency Modification Enable
36: External Stop Terminal 1
37: Run Command Switching Terminal 2
38: PID Integral Pause
39: Frequency Source X and Preset Frequency Switching
40: Frequency Source Y and Preset Frequency Switching
43: PID Parameter Switching
44: User-defined Fault 1
45: User-defined Fault 2
46: Speed Control/Torque Control Switching
47: Emergency Stop
48: External Stop Terminal 2
49: Deceleration DC Braking
50: Clear This Operation Time
51: Two-wire and Three-wire Switching
52: Reverse Prohibition
53: Single Terminal UP/DOWN Enable, Frequency Source Switching (Same as Function 18)
54: Terminal Activate UP, Deactivate DOWN
01 ✳️ 62464
P4-01 X2 Terminal Function Selection Same as P4-00 02 ✳️ 62465
P4-02 X3 Terminal Function Selection Same as P4-00 04 ✳️ 62466
P4-03 X4 Terminal Function Selection Same as P4-00 09 ✳️ 62467
P4-04 X5 Terminal Function Selection Same as P4-00 12 ✳️ 62468
P4-05 X6 Terminal Function Selection Same as P4-00 00 ✳️ 62469
P4-06 X7 Terminal Function Selection Same as P4-00 00 ✳️ 62470
P4-10 X Terminal Filter Time 0.000s~1.000s 0.010s 62474
P4-11 Terminal Command Mode 0: Two-wire Type 1
1: Two-wire Type 2
2: Three-wire Type 1
3: Three-wire Type 2
0 ✳️ 62475
P4-12 Terminal UP/DOWN Change Rate 0.001Hz/s~65.535Hz/s 1.00Hz/s 62476
P4-13 AI Curve 1 Minimum Input 0.00V~P4-15 0.00V 62477
P4-14 AI Curve 1 Minimum Input Corresponding Setting -100.0%~+100.0% 0.0% 62478
P4-15 AI Curve 1 Maximum Input P4-13~+10.00V 10.00V 62479
P4-16 AI Curve 1 Maximum Input Corresponding Setting -100.0%~+100.0% 100.0% 62480
P4-17 AI Filter Time 0.00s~10.00s 0.10s 62481
P4-18 AI Curve 2 Minimum Input 0.00V~P4-20 0.00V 62482
P4-19 AI Curve 2 Minimum Input Corresponding Setting -100.0%~+100.0% 0.0% 62483
P4-20 AI Curve 2 Maximum Input P4-18~+10.00V 10.00V 62484
P4-21 AI Curve 2 Maximum Input Corresponding Setting -100.0%~+100.0% 100.0% 62485
P4-22 AI2 Filter Time 0.00s~10.00s 0.10s 62486
P4-23 AI Curve 3 Minimum Input 0.00V~P4-25 0.00V 62487
P4-24 AI Curve 3 Minimum Input Corresponding Setting -100.0%~+100.0% 0.0% 62488
P4-25 AI Curve 3 Maximum Input P4-23~+10.00V 10.00V 62489
P4-26 AI Curve 3 Maximum Input Corresponding Setting -100.0%~+100.0% 100.0% 62490
P4-27 AI3 Filter Time 0.00s~10.00s 0.10s 62491
P4-28 HDI Pulse Minimum Input 0.00kHz~P4-30 0.00kHz 62492
P4-29 HDI Pulse Minimum Input Corresponding Setting -100.0%~+100.0% 0.0% 62493
P4-30 HDI Pulse Maximum Input P4-28~50.00kHz 50.00kHz 62494
P4-31 HDI Pulse Maximum Input Corresponding Setting -100.0%~+100.0% 100.0% 62495
P4-32 HDI Pulse Filter Time 0.00s~10.00s 0.10s 62496
P4-33 AI Curve Selection Units: AI1 Curve Selection
Tens: AI2 Below Minimum Input Setting Selection, Same as Above
Hundreds: AI3 Below Minimum Input Setting Selection, Same as Above
321 62497
P4-34 AI Below Minimum Input Setting Selection Units: AI1 Below Minimum Input Setting Selection
0: Corresponding Minimum Input Setting
1: 0.0%
Tens: AI2 Below Minimum Input Setting Selection, Same as Above
Hundreds: AI3 Below Minimum Input Setting Selection, Same as Above
000 62498
P4-35 X Terminal Active Mode Selection 1 0: High Level Active
1: Low Level Active
Units: X1
Tens: X2
Hundreds: X3
Thousands: X4
Ten Thousands: X5
000 62499
P4-37 AI Input Voltage/Current Selection Units: AI1
Tens: AI2
0: Voltage Input
1: Current Input
000 ✳️ 62501
P4-38 X1 Conduct Delay Time 0.0s~6553.5s 0.0s ✳️ 62502
P4-39 X2 Conduct Delay Time 0.0s~6553.5s 0.0s ✳️ 62503
P4-40 X3 Conduct Delay Time 0.0s~6553.5s 0.0s ✳️ 62504
P4-41 X4 Conduct Delay Time 0.0s~6553.5s 0.0s ✳️ 62505
P4-42 X5 Conduct Delay Time 0.0s~6553.5s 0.0s ✳️ 62506
P4-43 X6 Conduct Delay Time 0.0s~6553.5s 0.0s ✳️ 62507
P4-44 X7 Conduct Delay Time 0.0s~6553.5s 0.0s ✳️ 62508
P4-48 X1 Release Delay Time 0.0s~6553.5s 0.0s ✳️ 62512
P4-49 X2 Release Delay Time 0.0s~6553.5s 0.0s ✳️ 62513
P4-50 X3 Release Delay Time 0.0s~6553.5s 0.0s ✳️ 62514
P4-51 X4 Release Delay Time 0.0s~6553.5s 0.0s ✳️ 62515
P4-52 X5 Release Delay Time 0.0s~6553.5s 0.0s ✳️ 62516
P4-53 X6 Release Delay Time 0.0s~6553.5s 0.0s ✳️ 62517
P4-54 X7 Release Delay Time 0.0s~6553.5s 0.0s ✳️ 62518