5.14 Pd Group Communication Parameters
5.14 Pd Group Communication Parameters
ℹ️
Variable Frequency Drive Parameter Attribute Description
✅: Indicates that the parameter setting value cannot be changed when the variable frequency drive is in a running state.
❎: Indicates that the value of the parameter is the actual detected recording value and cannot be changed.
Pd Group: Communication Parameters
Function Code | Name | Setting Range | Factory Value | Attribute | DEC Address |
---|---|---|---|---|---|
Pd-00 | Baud Rate | 0: 300BPS 1: 600BPS 2: 1200BPS 3: 2400BPS 4: 4800BPS 5: 9600BPS 6: 19200BPS 7: 38400BPS 8: 57600BPS |
5 | ✅ | 64768 |
Pd-01 | Data Control Format | 0: No parity (8-N-2) 1: Even parity (8-E-1) 2: Odd parity (8-O-1) 3: No parity (8-N-1) |
3 | ✅ | 64769 |
Pd-02 | Local Address | 1~247 | 1 | ✅ | 64770 |
Pd-03 | Response Delay | 0~20ms | 2 | ✅ | 64771 |
Pd-04 | Communication Timeout | 0.0 (invalid) 0.1s~60.0s |
0.0 | ✅ | 64772 |
Pd-05 | Data Transfer Format Selection | 1: Standard MODBUS Protocol | 1 | ✅ | 64773 |
Pd-06 | Communication Reading Current Resolution | 0: 0.01A 1: 0.1A |
0 | ✅ | 64774 |
Pd-07 | Reserved | - | 0 | ✅ | 64775 |
Explore these documents to learn more.